• RT-CKX8 Air-Insulated Busway
  • RT-CKX8 Air-Insulated Busway
  • RT-CKX8 Air-Insulated Busway
  • RT-CKX8 Air-Insulated Busway

RT-CKX8 Air-Insulated Busway

Intro:The interior employs an isolated air-insulation design, ensuring both the safe clearance and creepage distance between phases significantly exceed the requirements specified by national standards. The phase-to-phase insulation within the equipment utilizes highstrength epoxy resin material, effectively enhancing the busway's dynamic and thermal stability to maintain reliable operation under extreme conditions.
  • RT-CKX8 Air-Insulated Busway
  • RT-CKX8 Air-Insulated Busway

Description

Product Features

The interior employs an isolated air-insulation design, ensuring both the safe clearance and creepage distance between phases significantly exceed the requirements specified by national standards. The phase-to-phase insulation within the equipment utilizes highstrength epoxy resin material, effectively enhancing the busway's dynamic and thermal stability to maintain reliable operation under extreme conditions. The enclosure is formed with a one-piece corrugated structure through bending technology, resulting in a compact size and elegant appearance while substantially improving the mechanical load-bearing capacity compared to conventional busways.

Scope of application

Air-insulated busways are suitable for AC three-phase four-wire and three-phase five-wire systems, with a frequency of 50–60 Hz, rated voltage up to 660V, and rated operating current ranging from 250A to 5000A. They serve power distribution functions, connecting low-voltage distribution panels to medium and large loads, and are primarily used in modern workshops, industrial plants, and high-rise buildings

Structural characteristics

● Air-insulated busways feature a compact design with excellent corrosion resistance, heat dissipation, and grounding performance. Their unique double-layer hollow structure provides each enclosure segment with pipe-like bending resistance, significantly enhancing the overall system's torsional strength.

● The system incorporates standard single-arm locking vibration-damping connectors for reliable and convenient installation.

● Power tap-off openings can be flexibly arranged on both top and bottom surfaces without compromising bending resistance. These tap-off interfaces achieve IP5X protection rating (compliant with IEC 60529).

◎ Insulation Configuration

● Busbar insulation utilizes high-efficiency polyester film, which offers superior high-temperature resistance (no toxic gas emission under extreme heat) and dielectric properties, rated as Class B insulation. Alternatively, premium polytetrafluoroethylene (PTFE) oriented film (SFM-3) can be used, featuring an extreme temperature range (-180℃ to +250℃ ), single-layer withstand voltage of 6000V, Class C insulation rating, and insulation aging life exceeding 50 years, representing the highest-performance insulation material currently available.

Work environment

● Ambient Temperature: Upper limit: +40℃ ; Lower limit: -25℃ ; Altitude: ≤ 2000m

● Humidity: Relative humidity ≤ 50% at +40℃ ; higher relative humidity permitted at lower temperatures. Condensation: Possible; Seismic Intensity: Designed for magnitude 6; Installation: Indoor/Outdoor

● Insulation Resistance: Each enclosed busway unit shall have insulation resistance ≥ 100MΩ (measured with 2500V megohmmeter)

● Dielectric Strength: Each busway section withstands 1-minute power-frequency dry withstand voltage test before shipment. Test values comply with national standards for power-frequency and lightning impulse withstand voltages.

● Grounding System: Complies with IEC 60364-5-54 requirements.

● Protection Rating: Indoor type: IP40; Outdoor type: IP43/IP55

● Load Performance: At rated current, enclosure temperature rise meets GB 763-90 standards for AC high-voltage equipment under continuous operation.

● Short-Circuit Performance: Dynamic and thermal stability tests conform to GB 2706-89 standards for AC high-voltage equipment testing methods.

Performance parameter table

Rated Current
(Ambient Temperature -5 to 50°C)
A 250 400 630 800 1000 1250 1600 2000 2500 3150 4000 5000
Rated Short-Time Withstand Current KA(IS) 30 30 30 50 50 50 80 80 80 80 130 130
Impedance Z mΩ/m 0.134 0.108 0.089 0.069 0.067 0.041 0.032 0.024 0.021 0.016 0.012 0.011
Resistance R mΩ/m 0.130 0.105 0.086 0.087 0.055 0.039 0.030 0.023 0.018 0.015 0.011 0.009
Reactance X mΩ/m 0.064 0.062 0.054 0.045 0.033 0.026 0.021 0.013 0.007 0.021 0.013 0.007
Rated Voltage V <1000 <1000 <1000 <1000 <1000 <1000 <1000 <1000 <1000 <1000 <1000 <1000
Voltage Drop
COS 0=0.7
mV/A · m 0.237 0.204 0.171 0.137 0.113 0.079 0.062 0.043 0.031 0.044 0.026 0.020
Voltage Drop
COS 0=0.8
mV/A · m 0.247 0.210 0.175 0.139 0.115 0.081 0.063 0.045 0.030 0.045 0.026 0.021
Voltage Drop
COS(J)=0.9
mV/A · m 0.251 0.212 0.174 0.138 0.114 0.080 0.083 0.045 0.033 0.039 0.027 0.020
Voltage Drop
COS 0=1.0
mV/A · m 0.225 0.182 0.148 0.116 0.096 0.067 0.052 0.040 0.031 0.026 0.020 0.016